Measurement Functions | Ground resistance |
Interface | RS232/RS485, HANDLER, USB |
Standard Configuration | AC 5A~40A |
Comparator | Upper and lower limit sound and light alarm |
Protect Function | Over-voltage protection |
Ground Impedance | 0 ~ 600mΩ accuracy ±(2%× Read the numerical +5 dgt ) resolution 0.1 mΩ |
Current Setup Range | AC 5A ~ 40A,accuracy ±(2%× reading +5 dgt ), resolution 0.1A |
Power Supply | AC 220V 50Hz power <200W |
Dimension & Weight | 250mm×120mm×320mm 10kg |
Accessories | power cable RS232 communication cable ATL900A test clamp |